7P three phase direct connection 4G energy meter
The SEM4MT-4G is an IoT three-phase DIN rail energy meter for low- and medium-voltage systems. It combines measurement, metering and control: three-phase AC measurement and calculation, energy accumulation, RS485 communication, and 4G wireless data transmission to a remote platform. Multi-tariff metering, maximum demand and one relay alarm output are available as options.
The meter uses a 7-module DIN rail housing with a segment LCD and four keys. It is intended for power, telecommunications, railway, transport, environmental protection, petrochemical and steel installations, where the consumption of AC equipment has to be monitored.
Power utilities, telecommunications, railway and transport, environmental protection, petrochemical and steel installations — anywhere three-phase AC consumption has to be measured, billed and uploaded.
Item | Specification |
|---|---|
Distribution network | Three-phase three-wire, three-phase four-wire |
Voltage – rated | AC 100 V, 220 V, 380 V |
Voltage – overload | 1.2 × continuous, 2 × for 10 s |
Voltage – burden | < 0.1 VA per phase |
Voltage – impedance | > 1 MΩ |
Voltage – accuracy | Class 0.5, true RMS measurement |
Current – rated | Direct connection 10(40) A, 20(80) A |
Current – overload | 1.2 × continuous, 10 × for 1 s |
Current – burden | < 0.4 VA per phase |
Current – impedance | < 10 mΩ |
Current – accuracy | Class 0.5, true RMS measurement |
Frequency | 40–65 Hz, accuracy ±0.01 Hz |
Power | Three-phase active class 1, reactive class 2 |
Energy | Four-quadrant metering; active class 1, reactive class 2 |
Multi-tariff (optional) | 4 profiles, 4 tariffs, 12 time periods |
Maximum demand (optional) | Monthly maximum demand for the last three months |
Display | Segment LCD, programmable |
Auxiliary supply | Three-phase voltage input, AC 85–456 V |
Supply burden | ≤ 4 VA |
Digital interface | RS-485, Modbus-RTU (DL/T645-2007 optional) |
Network interface | 4G |
Pulse output | 1 active energy pulse output |
Relay output (optional) | 1 output, 5 A / 250 V AC, 5 A / 30 V DC |
Operating conditions | −10 to +55 °C, altitude ≤ 2000 m, 93 % RH, non-condensing, no corrosive gas |
Storage conditions | −30 to +70 °C |
Dielectric strength | Input to supply > 2 kV; input to output > 2 kV; supply to output > 2 kV |
Insulation | Input, output and supply to case > 5 MΩ |

Please leave us your messages and feedback, our sales engineers are always right beside you.